Permit: T02CM05206

Parcel: 141090300


Addresses:

7960 S KOLB RD


Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Permit Number - T02CM05206

Inspection Description - BUILDING PRE-SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2003 BUILDING PRE-SLAB Approved IVRS - Inspection 0000*
01/08/2003 BUILDING PRE-SLAB Denied IVRS - Inspection 0999*1.) COMPACT SLAB BASE TO 95%. MINIMUM.
2.) ANCHOR BOLTS @ DO NOT CONFORM TO TABLE ON PAGE 2.
3.) ANCHOR BOLTS NOT INSTALLED AT A,G,E,C, OR B.
4.) CAN NOT LOCATE DETAIL V/2 OR T/2 ARE THEY WHAT I'VE MARKED?
5.) NO WIRE MESH PER DETAILS @ SITE.