Permit: T02CM05120

Parcel: 12517035A


Addresses:

3821 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM05120

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
05/09/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) Permanently label equipment on roof.
2.) condensate cannot drip out of the scuppers extend to within 6" of dirt.
recall for inspection
3.) Provide guard rails on service side of unit on lower roof.
03/05/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
03/04/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O
02/28/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*STILL NEED TO SEE DUCT SMOKE DETECTORS.
FINISH INSTALLING CONDENSATE DRAIN LINES.
FUSE A/C UNITS.
OK FOR TEMP C OF O.
OK TO CLEAR GAS.