Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*TUB FLOW OK 2. OK TO COVER ALL AREAS. |
|
| 01/08/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) ABS DWV THRU ROOF OK NEED TO SEE TUB FLOW TEST 2.) PEX OK 3.) CLOSET FLANGES OK 4.) SEWER OK WATER TEST OK 5.) OK TO COVER ALL AREAS. |
|
| 01/06/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) SEE NOTE FROM 1/3/03 2.) NO PLANS OR PERMIT ON SITE. 3.) NO STRUCTURAL CONDITION REQUIRING AIR ADMITTANCE VALVE. 4.) PEX TO BE SUPPORTED EVERY 3 FEET 5.) ABS HORIZONTAL TO BE SUPPORTED 6.) FHA STRAPS REQ'D ON UPPER AND LOWE PLATES 7.) 50# MINIMUM TEST FOR WATER. |
|
| 01/05/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) H2 TEST REQ'D ON PLBG. TOP OUT. 2.) SECURE PIPES THRU OUT. 3.) 3" ABS VENT HAS BREACHED REQ'S FIRE WALL SEPARATION. RE INSPECTION FEE DUE PRIOR TO NEXT INSPECTION. |
|
| 01/03/2003 | PLUMBING - INTERMEDIATE | Denied | NOT READY RE-FEE RATED WALL BETWEEN UNITS HAS BEEN COMPROMISED | |
| 12/31/2002 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* |