Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM04572
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) OK TO DRYWALL. | |
10/14/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST ON WASTE SYSTEM. 2.) CAN NOT HAVE FLAT FACED BUSHINGS ON HORIZONTAL DRAINAGE MUST USE BELL REDUCE SEE SECTION 311 94 UPC INTERPETATION. 3.) MUST HAVE 2" P-TRAPS ON 2" TRAP ARMS FOR TUB & SHOWER UNITS. 4.) MUST STRAP DOWN ALL HORIZONTAL WASTE EVERY 4'-0" WITH APPROVED STRAPS. P-TRAP IS NOT APPROVED MATERIAL. |