Permit: T02CM04433

Parcel: 134110670


Addresses:

7909 E BEVERLY ST

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
01/06/2003 ROOF NAILING Approved IVRS - Inspection 0000*
01/02/2003 ROOF NAILING Denied IVRS - Inspection 0999*/ 1) PROVIDE TRIMMERS AT WINDOW HEADER 2) DOUBLE HEADER (2-2 X 4 ON EDGE AT DOOR 3) PROVIDE PROPER BLOCKING FOR NAILING AT ROOF 4) SECURE ELECTRIC PER NEC 5) J-BOXES REQUIRED TO BE ACCESSIBLE 6) PROVIDE ANTI-SCALD DEVICE FOR SHOWER 7) GFCI REQUIRED AT EXT. ON SEPERATE CIRCUIT 8) WATER TEST REQUIRED AT ABS 9) EXHAUST FAN DUCT REQUIRED TO BE INSTALLED 10) ROMEX CONNECTOR TO METAL BOXES 11) DOOR REQUIRED TO BE FRAMED IN 12) AB REQUIRED WITHIN 12" OF SPLICE OR DOOR 13) WALL TO BE FRAMED IN FOR SHOWER 14) GFCI NOT A PROPER LOCATION AT LAV
12/27/2002 ROOF NAILING Denied IVRS - Inspection 0999* PLAN DOES NOT REFLECT AS BUILDT. WORK SUBSTANDARD. NOT READY FOR INSPECTION. I WOULD LIKE TO MEET WITH CONTRACTOR IF POSSIBLE @ NEXT INSPECTION
12/17/2002 ROOF NAILING Denied IVRS - Inspection 0999*/ 1) SECURE ROMEX PER CODE 2) J-BOX REQUIRED TO BE ACCESSIBLE 3) PROVIDE NAIL PROTECTION AT BORED HOLES 1 1/4" 4) DOUBLE TOP PLATE REQUIRED AT NORTH WALL PER PLAN 5) H.25 EACH RAFTER TO TOP PLATE PER PLAN