Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1.) ABS DWV THRU ROOF OK WATER TEST OK 2.) PEX PIPING OK PRESSURE TEST OK 3.) TUBS OK 4.) CLOSET FLANGES OK 5.) OK TO COVER WALLS. 6.) CONTRACTOR WILL HAVE PLUMBER REPLACE NIAL GUARDS ON BOTTOM PLATE WITH FHA STRAPS. |
|
| 11/12/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) SEE 103.5.4.2. RESPONSIBLITY OF THE HOLDER OF THE PERMIT. TO INSURE WORK IS READY BEFORE CALLING INSPECTIONS 1.) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION. 2.) A TRAP ARM MAY NOT CHANGE SIZE. 3.) MINIMUN 2 PIPE DIAMETER BETWEEN WEIR OF TRAP AND POINT OF VENT. 4.) 15" MINIMUM FROM SIDEWALL TO CENTER OF WATER CLOSET. 5.) SEPARATION BETWEEN HOT AND COLD LINES TO ELIMINATE HEAT TRANFERENCE. 6.) ABS SUPPORT HORIZONTAL. |
|
| 11/08/2002 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* NOT READY FOR INSPECTION. |