Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM04105
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*BE SURE YOUR LAYOUT PROVIDES THE NECESSARY LIGHTING & POWER OUTLETS NEEDED. | |
11/14/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS. | |
11/06/2002 | ELECTRIC - INTERMEDIATE | Denied | CORRECTIONS REQUIRED: 1.) PLANS MUST BE REVISED TO REFLECT THE RELOCATION OF THE ELECTRICAL PANELS AND TRANSFORMER. 2.) THE TRANSFORMER AND PANEL NEXT TO IT MUST MEET THE CLEARANCE REQUIREMENTS OUTLINED ABOVE. 3.) THE ELECTRICAL SPECS. DO NOT ALLOW THE USE OF M.C. CABLE. SEE NOTES 4-5 ETC. REFER THIS TO YOUR ENGINEER MR J. MCGETRICK FOR HIS REVIEW AND NOTIFY MALL MANAGEMENT AS THEY DO NOT ALLOW THE USE OF MC CABLE FOR GENERAL WIRING ON THE PREMISES. THANK MAC. |
|
11/01/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*NO ELEC. ROUGH INSP. TILL WE HAVE THE APPROVED ELECTRICAL PLANS PROVIDE THE APPROVED SET OF ELECTRICAL PLANS NO SIGNATURE OF PLAN REVIEW BRING SET TO RANDY SCHULER 201 N. STONE FOR SIGNATURE. PANEL DOES NOT HAVE THE MINIMUM REQUIRED WORK CLEARANCE S/B 30" WIDTH BY 36" DEPTH. BOND BOTH END OF 1/2" EMT AT TRANSFORMER ALSO S/B CONNECTED TO BUILDING STEEL PIGTAIL EQUIP. GROUNDING CONDUCTOR AT RECEPTS AT INTERMEDIATE INSPECTIONS. |