Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) LABEL CIRCUITS @ SVC PANEL 2.) PROVIDE COVER @ J-BOX IN W/H 3.) PROVIDE ANIT SYPHON DEVICES @ HOSE BIBS. 1.) A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER 2.) TIGHTEN 2" EMT FITTINGS. 3.) IDENTIFY NEUTRAL AT TERMANAL. 4.)MULTIPOLE TERMANATIONS AT BOND BUSHING LUG. |