Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/11/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
RIVER ELECTRIC IS CONTRACTOR ON JOB. 1. FINISH INSTALLATION OF FUSES AND REJECTION PINS 2.) PLEASE RECALL AFTER TESTING AND RE LABELING OF BREAKERS OK TO CLEAR TEMP POWER |
| 09/05/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SERVICE NEEDS TO BE AS PER ALL APPLICABLE CODES. 2.) HAVE LICENSED ELECTRODE CONTRACTOR PROVIDE A LETTER ON COMPANY LETTERHEAD VERIFYING WORK LIABILITY FOR THIS PROJECT. 3.) COULD NOT FIND VERIFICAITON OF PERMITS FOR BACK BUILDING PLEASE VERIFY PERMITS FOR BACK BUILDING ADDITION. |
| 08/30/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) R TYPE FUSE AND REJECTION CLIPS NEED TO BE INSTALLED 2.) WE HAVE MULTIPOLE TERMANATIONS UNDER LUGS AT MAIN DISCONNECTS 3.) NO MORE THAN 6 THROW OF HANDERS ALLOWED AT MAIN SERVICE WE HAVE 8-ALSO PANEL HAS BEEN MODIFIED FOR MAIN BREAKER. NEED DRAWING TO VERIFY LOAD CALCULATION. HAVE 1120 AMPS WORTH OF DISCONNECTS. 4.) FINISH CLEAN UP AND INSTALLATION OF ROOF EQUIPMENT IF EQUIPT. NOT IN USE PLEASE DISCONNECT. 5.) PLEASE VERIFY ROOM ADDITION TO BACK OF BONDING FOR OLD PERMITS. |
| 08/23/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MISSING FACE PLATES 2.) HAVE LICENSED L-11 ELECTRICAL CONTRACTOR CHECK BOX GROUNDING AT DRIVE THRU WINDOW AND ALL WORK TO BE DONE. 3.) FILL UNUSED OPENINGS IN JUNCTION BOXES. 4.) OPEN BOXES ON TOP OF WALK IN COOLER 5.) FLEX CONDUIT NEXT TO GRILL TO BE INSTALLED AS PER CODES. 6.) UNSAFE CORD CAP CONNECTION AT ICE MACHINE. 7.) NEED ACCESS TO STORAGE ROOM ON BACK ARE MAIN DISCONNENTS LOCATED THERE? 8.) DETERIORATION AT A/C UNITS ON ROOF BOTH CONDUCTORS AND SEALTITE. 9.) COOLER TO BE WIRED CORRECTLY NOT EXTENTION CORD REPLACE DETERIORATED CORDS. 10.) OPEN CONDUTORS 11.) MECHANICAL INSPECTOR TO DETERMINE HOOD CONDITION 882-2784 ALFONSO. |