Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/05/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 12/18/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) MISSED NAILING AT BEAM OVER TO FRONT WALL AT FRONT DOOR, MARKED IN BLACK 2) INSTALL ALL OSB ON WLLS FOR EXT. CLIP INSP (H2.5'S VERIFIED AT LEDGERS OK TO COVER 3) CROSS MARKED ON GARAGE DECK BROKEN OSB BLOCK BELOW FOR SUPPORT 4) FRONT DOOR PLATE OFF SLAB 5) SEE POST TENSION PLAN ALL CABLES TO BE PULLED BEFORE ROOF SHEATHING IS APPLIED 6) ALL BOLTS FOR H.D.'S TO BE SPECIAL INSPECTED (EPOXY SET) |
| 12/17/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0925*/ 1) NO PLANS/PERMIT ON SITE |