Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM03451
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2002 | PLUMBING - FINAL | Approved | CORRECTIONS MADE OK 2.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS. | |
10/28/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) A TRAP ARM MAY ONLY CHANGE DIRECTION 90 WITHOUT AN ADDITIONAL CLEAN OUT. 2.) CHANGES OF DIRECTION ON INDIRECT WASTE PIPING MAY REQUIRE ADDITIONAL CLEAN OUTS. 3.) PLUMBER TAPE IS NOT APPROVED STRAP. | |