Permit: T02CM03418


Addresses:

1720 W IRVINGTON RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/22/2003 MECHANICAL - FINAL Approved
01/06/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O.
01/02/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
NOTE ROOF TOP UNIT DATA PLATE MINIMUM CIRCUIT 65.9. AMP.
MAX FUSE SIZE 70 AMPS. 60 AMPS NOT SUFFICENT.
WALK IN BOX TAGGLE SWITCH AT AIR HANDLERS?? PLEASE PROPERLY COMPLETE. BEFORE RECAULKING
12/31/2002 MECHANICAL - FINAL Partial Approval FRAME COMB. ROOF TOP UNIT UNIT AS FUSED, NOT CORRECT.
2.) COND PVC PIPING
NEEDS TO BE PAINTED WHERE
EXPOSED
3.) WALL IN BOX A/H NEED TAGGLE SWITCH AT EACH UNIT.