Inspection History Details
Permit: T02CM03418
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2003 | ELECTRIC - FINAL | Approved | ||
| 01/03/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) LABEL CB'S FOR MDP PANEL. 2.) SEAL HOLE ON GUTTER. 3.) SHEET E-5 STATES LABEL ALL PNLS WITH SERIES RATING INFO REQUIRED ON PLAN. 4.) SERVICE HAS BEEN INCREASED FROM 400 A TO 600A PROVIDE CITY APPROVED STAMP NOT JUST ENGINEERS 5.) ROOF TOP HEATING & COOLING UNIT TO BE CORRECTED UNIT CALLS FOR 70A FUSE 60 INSTALLED 6.) CONNECT IR9G CONTRAL BY REAR DOOR. L7.) LED ON TOP OF ISLAND CANOPY TIGHTEN ARE LOOSE SEALTIGHT FITTINGS NON ME TALK FOR FINAL 1-7 NEED TO BE COMPLETED OK TO CLEAR FOR TEMPORARY C OF O. 600A SER REVISION APPROVED BROWN BOX DISPENSER COMPLIANCE APPROVED |
|
| 01/02/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*CANCELED BY CONTRACTOR. |