Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) ABS DWV THRU ROOF OK WATER TEST OK 2.) COPPER WATER TEST OK 3.) OK TO COVERK ALL AREAS. NOTE: YOU MAY NOT TERMINATE CONDENSATE WASTE INTO SINK TAILPIECE. |
|
| 03/07/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) REMOVE JIM CAPS AND CONNECT PIPING WITH SL X 5L COUPLING. TEST THRU THE CLEAN OUTS. 2.) SEVERAL SECTIONS OF VENT ARE BACKPITCHED 3.) CHECK SINK DRAINS AND CORRECT BACKPITCH 4.) A SINK IS NOT AN APPROVED LOCATION TO TERMINATE CONDENSATE PIPING. 5.) FITTING ADDED AFTER ROUGH/SOIL MUST BE WATER TESTED. 6.) CLEAN OUTS MAY NOT CONNECT HORIZONTALLY TO HORIZONTAL DRAIN LINES. 7.) WHEN PROVIDING A SECTIONAL TEST, AT LEAST THE UPPERMOST TEN FEET OF THE NEXT PROCEEDING SECTION MUST BE FILLED WITH WATER SO THAT NO JOINT OR PIPE IN THE BLDG SHALL HAVE BEEN TESTED WITH LESS THAN 10' HEAD FO WATER. 8.) DO NOT INSULATE PLUMBING AREAS 9.) SEE NOTE #4 PLAN APPROVED IN ERROR 10.) REC'D LETTER FROM ARCHETECT APPROVING PVC YARDWATER PIPING. |
|
| 01/21/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*COPPER IN WALLS ONLY/NEED REVISED PLAN BY NEXT INSP. |