Permit: T02CM02897

Parcel: 205661280

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/02/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/24/2004 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PROVIDE PROOF OF APPROVED INSPECTIONS FOR INSPECTIONS 1045, 1015 AND 1010 2) TAP NEED TO BE HARD PIPED
02/18/2004 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) SERVICE PANEL 20 AMP BREAKER 14 GA. WIRE, PUT WIRE IN CONDUIT, ALSO #10 EACH TO BE IN CONDUIT 2) USE ROMEX CONNECTOR 3) PLUG HOLE 4) GFCI NOT TRIPPING AT REAR PORCH 5) OVEN AT PORCH EXTEND RIGID PIPE TO OUTSIDE OF UNIT 6) NEED CLEAN OUT AT KITCHEN SINK NORTH 7) TWO OUTLETS EACH SIDE OF COOK TOP WON'T TRIP GFCI 8) NEED CLEANOUTS AT ALL KITCHEN SINKS 9) LOOSE OUTLET IN GIRLS BATH 10) CAP OFF SEWER AT URINAL 11) HEATE PUMP, DISCONNECT NEED #8 CU. FROM UNIT TO DIS. MISSING COVER PLATE AT DIS. 12) NEED FIREPLACE CAULK AT BOTH FIREPLACES GAS LINE IN HEARTH 13) NEED EXPANSION TANK 14) NEED LOAD CALC. FOR SERVICE EQUIPMENT. PLANS ON ITEMS SHOWN ARE NOT THE SAME SOME CHANGES MADE, MAYBE