Permit: T02CM02721

Parcel: 128010010

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM02721

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
09/05/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*NEED TO SEE FIRE DAMPER OPENINGS. ANGLE IRON NOT PROPERLY INSTALLED. PROVIDE APPROVED FIRE DAMPER ACCESS DOOR ON SUPPLY DUCT. STILL NEED TO SEE UNIT ON ROOF. RECALL TO INSPECT DAMPER OPENINGS. PROVIDE LETTER FROM ARCHITECT, IF PARTITION IS NOT FIRE RATED, WHY FIRE DAMPERS?