Permit: T02CM02654

Parcel: 127070080

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/29/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/26/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) USE AN APPROVED FITTING AT LB-CHASE NIPPLE NOT APPROVED
03/23/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) NEED TO SEE CONNECTION TO HANDRAILS 2) WORKING CLEARANCE NEEDED FOR FORMER DISCONNECT 3) CONDUCTOR ? IN GUTTER 374.5 4) NEED REJECTION PINS AND FUSES