Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) USE AN APPROVED FITTING AT LB-CHASE NIPPLE NOT APPROVED |
| 03/23/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NEED TO SEE CONNECTION TO HANDRAILS 2) WORKING CLEARANCE NEEDED FOR FORMER DISCONNECT 3) CONDUCTOR ? IN GUTTER 374.5 4) NEED REJECTION PINS AND FUSES |