Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM02632
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*CORRECTIONS MADE OK PLUMBING FINAL OK 2.) OK FOR C OF O PENDING ANY OTHER INSPECTION. |
|
03/10/2003 | PLUMBING - FINAL | Denied | ALL ROOF PENETRATIONS REQUIRE PROPERLY SIZED FLASHING I NEED ACCESS TO ALL AREAS LEAD FLASHING OBSTRUCTS CROSS SECTIONAL AREA OF VENT.2.) WATER CLOSETS REQUIRE 15" FROM CENTERLINE TO SIDEWALL OR OBSTRUCTION. 3.) URINAL (HC) REQUIRES 15" FROM SIDEWALL TO CENTER. 4.) WHAT PROTECTS THE POTABLE WATER FROM BACKFLOW/SIPHORAGE WITHIN THE PARK. |
|
03/04/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FOR INSPECTION. | |
12/04/2002 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) FITTINGS NOT INSTALLED PER MANUFACTURER'S INSTALLATION RECOMMENDATIONS. 2.) POINT OF VENT MAY NOT BE BELOW THE WEIR OF THE TRAP. |