Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
1.) SOIL WATER TEST IS OK 2.) BLDG. DRAIN IS STUBBED OUT @ TWO WAY C.O. ONLY. 3.) OK TO BACKFILL TRENCH. 4.) NOTE: WILL REQUIRE A REVISED & APPROVED DRAWING ON WASTE & VENT SYSTEM AS REQUESTED. |
| 10/07/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) THERE IS A LEAK @ 3 X 2 WYE ON 2" RISER @ WEST SIDE OF BLDG. 2.) RE TEST SYSTEM. 3.) MUST RED LINE APPROVEL PLAN THE WAY PLUMBING ROUGHED IN WASTE. 4.) WILL REQUIRE A REVISED & APPROVED DRAWING ON WASTE SYSTEM PRIOR TO FINAL INSPECTION. |