Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000*WHAT IS THE REFERENCE OF THE LABEL THAT STATES "LNG LANDING SUITABLE FOR (3) LUGS PER PASS & NEUTRAL" WE HAVE 4 LUGS AT EACH PHASE AND 5 LUGS AT THE NEUTRAL 2.) PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD FOR TORQUE VALVES OF SERVICE EQUIPMENT. 3.) REJECTION PINS ARE NEEDED. 4.) PLEASE PROVIDE APPROVED PLANS ON SITE. |
|
| 05/14/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*PLEASE OPEN TILE AS PER #2 LAST INSPECTION. 2.) BLANK LIGHTS OF OUTSIDE AND BELOW 8' INSIDE. 3.) PLEASE HAVE ELECTRICAN OPEN SERVICE FOR INSPECTION. |
|
| 05/09/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) SUPPORT M/C CABLE WITHIN 12" OF CANS. 2.) PLEASE OPEN TILE INROOM 127 & HALLWAY FOR LIGHTS NOT INSTALLED LAST INSPECTION. |
|
| 04/29/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* |