Permit: T02CM02411

Parcel: 109250550

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/15/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*WHAT IS THE REFERENCE OF THE LABEL THAT STATES
"LNG LANDING SUITABLE FOR (3) LUGS PER PASS & NEUTRAL" WE HAVE 4 LUGS AT EACH PHASE AND 5 LUGS AT THE NEUTRAL
2.) PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD FOR TORQUE VALVES OF SERVICE EQUIPMENT.
3.) REJECTION PINS ARE NEEDED.
4.) PLEASE PROVIDE APPROVED PLANS ON SITE.
05/14/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*PLEASE OPEN TILE AS PER #2 LAST INSPECTION.
2.) BLANK LIGHTS OF OUTSIDE AND BELOW 8' INSIDE.
3.) PLEASE HAVE ELECTRICAN OPEN SERVICE FOR INSPECTION.
05/09/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) SUPPORT M/C CABLE WITHIN 12" OF CANS.
2.) PLEASE OPEN TILE INROOM 127 & HALLWAY FOR LIGHTS NOT INSTALLED LAST INSPECTION.
04/29/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*