Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 07/18/2003 |
PLUMBING - SEWER HCS CONNECT |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS MADE-OK 2) WATER TEST-OK, TRANSITION FITTINGS OK 3) OK TO BACKFILL |
| 07/16/2003 |
PLUMBING - SEWER HCS CONNECT |
|
Denied |
1) PIPING IS TO BE LAID ON A FIRM BED (NO BRIDGING ALLOWED) WITH A UNIFORM PITCH OF 2 PERCENT (NO BACK PITCHED SECTION) ? THE PIPE HELPS SUPPORT IT |