Permit: T02CM02333

Parcel: 114512000

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
08/08/2003 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*/ 1) PLEASE NOTE GAS LINE HAB BEEN APPROVED BY TV 12/20/02
08/30/2002 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection 0999*1.) MUST USE PROPER TRANSISION GLUE @ CONNECTION. WHERE SDR-35 AND ACH 40 CONNECT. 2.) PRIVATE SEWER REQUIRE A FLEXIBLE COMPRESSION JOINT NO CLOSER THAN 12" AND NO THAN 3FT FROM THE MANHOLE SEE SECTION 719.6 94 UPC 3.) RE TEST SYSTEM.
08/29/2002 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION @ THIS TIME.