Permit: T02CM02333

Parcel: 114512000

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/19/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP 0820AM SUBJECT TO ALL OTHER INSPECTORS. ALL INSPECTORS HAV SIGNED OFF OK TO CLEAR ECO
08/06/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) REJECTION PINS ARE NEEDED AT DISCONNECTS 2) WE HAVE MULTIPULE TERMINATIONS AT NEUTRAL BAR 3) FUSE TO BE AS PER PLAN 4) AN APPROVED EXTENDER RING IS NEEDED WHERE COMBUSTIBLE 370.20 SUPPORT DEVICE-AND IF MORE THAN 1/4" FROM BOX TO SURFACE AT NON COMBUSTIBLE 5) SWITCHES TO BE GROUNDED 380.9 6) FINISH ROOF 7) INSTALL ALL PLATES
08/01/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK 2" PVC LAST RUNS TO DISCONNECTS
07/30/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) MAINTAIN 24'' OR COVER IN PARKING LOT AS PER 300.5
07/29/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
07/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* OK 1" & 2" PVC IN DRIVEWAYS AS MARKED