Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM02071
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*OK FOR C OF O. | |
09/24/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) SEWER VENT STILL NOT EXTENDED 2' ABOVE AIR INTAKE. 2.) WATER LEAKING FROM MAKE UP AIR UNIT. 2.) SEAL AROUND WATER SUPPLY LINE AT ROOF JACK FOR MAKE UP AIR UNIT. SEAL AROUND REFER LINES TO CONDENSOR PENETRATION THRU ROOF. 4.) PLUG ENDS OF UNUSED ELEC. CONDUITS. | |
09/12/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) RAISE SEWER VENTS 2' ABOVE AIR INTAKE INTO BLDG. 2.) PROVIDE SUN PROTECTION OVER CANVAS CONNECTORS 3.) FINISH INSTALLATION OF CONDENSOR. 4.) BLOCK & CLAMP CONDENSATE DRAIN LINES 5.) FINISH DRAIN ON MAKE UP AIR UNIT. 6.) TYPE I EXHAUST TERMINATIONS DO NOT COMPLY WITH |