Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O. |
| 09/24/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SEWER VENT STILL NOT EXTENDED 2' ABOVE AIR INTAKE. 2.) WATER LEAKING FROM MAKE UP AIR UNIT. 2.) SEAL AROUND WATER SUPPLY LINE AT ROOF JACK FOR MAKE UP AIR UNIT. SEAL AROUND REFER LINES TO CONDENSOR PENETRATION THRU ROOF. 4.) PLUG ENDS OF UNUSED ELEC. CONDUITS. |
| 09/12/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) RAISE SEWER VENTS 2' ABOVE AIR INTAKE INTO BLDG. 2.) PROVIDE SUN PROTECTION OVER CANVAS CONNECTORS 3.) FINISH INSTALLATION OF CONDENSOR. 4.) BLOCK & CLAMP CONDENSATE DRAIN LINES 5.) FINISH DRAIN ON MAKE UP AIR UNIT. 6.) TYPE I EXHAUST TERMINATIONS DO NOT COMPLY WITH |