Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2002 |
MECHANICAL - INTERMEDIATE |
|
Approved |
|
| 08/29/2002 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*INSPECTED GREASE DUCTS & SHAFTS OK TO COMPLETE HOODS, FANS TO GREASE DUCTS. |
| 08/14/2002 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*DEVELOPED CHASE LOOKING GOOD. OK TO COVER FACE. |
| 08/12/2002 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*TYPE I HOOD DUCTS IN RIDGID 1 HR. ENCLOSURES DO NOT HAVE FULL SIX (6) INCH CLEARANCE AS PE SEC. 506.3.11. THIS WAS PLAN APPROVED UNDER EXCEPTION #2. UNDER SEC. 506.3.11. 2.) OK TO START HANGING HOODS. 3.) SEAL ALL PENETRATIONS IN CHASE PRIOR T0 SEALING FRONT FACE. |