Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM02009
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2003 | PLUMBING - FINAL | Approved | 1) CORRECTIONS MADE OK 2) PLUMBING FINAL OK 3) OK FOR C OF O PENDING ANY OTHER INSPECTION 4) LAST INSPECTOR TO LEAVE GAS CARD | |
| 08/20/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) H.C. WATER CLOSET FLUSH HANDLE TO BE ON WEST SIDE OF STALL. 2) ALL FIXTURES TO BE CAULKED. 3) REQUIRED 12" CLEARANCE IN FRONT OF CLEAN-OUT. 4) TRAP PRIMER TERMINATION WILL CAUSE SPLASHING, 5) JANITOR SINK TO BE CAULKED. 6) LEAK AT CONDENSATE 90 DEGREE ABOVE JAN. SINK. 7) URINAL MAX. HT IS 17" AFF. |