Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM01722
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/14/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*OK FOR C OF O. | |
06/12/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE PERMANENT LABELS ON ROOF TOP EQUIPMENT. 2.) LABEL AIR HANDLER #2 MARK DATA PLATE. 3.) CIRCUIT BREAKERS TO CONDENSORS ARE OVERSIZED. SEE DATA PLATE ON EQUIPMENT. 4.) CHECK FOR PROPER AMPERAGE ON HEAT STRIPS FOR AIR HANDLERS 2 & 3 #1 IS OK. OK FOR TEMP C OF O. RECALL FOR FINAL. |