Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T02CM01722
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000*SECONDARY DRAIN PANS NOT CENTERED CORRECTLY UNDER AIR HANDLERS UNITS 1 & 3. 2.) SEAL HOLES IN SUPPLY DUCT WHERE SMOKE DETECTOR WERE REMOVED. 3.) LABEL AIR HANDLERS W/UNIT NUMBER. 4.) UNIT #1 NEEDS MORE INSULATION ON SUCTION LINE. 5.) MARK DATA PLATES ON AIR HANDLERS W/PROPER HEAT KIT INSTALLED. BE SURE OVER CURRENT PROTECTION CORRSPONDS W//DATA PLATE. WILL CHECK ON FINAL. OK FOR PARTIAL CEILING TILES | |
06/05/2002 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) PROVIDE ADEQUATE ACCESS FOR SERVICE ON AIR HANDLERS. 2.) RELOCATEDUCT SMOKE DETECTORS TO THE RETURN AS PER 2000 IMC. RECALL FOR INSPECTION. |