Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/07/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*SECONDARY DRAIN PANS NOT CENTERED CORRECTLY UNDER AIR HANDLERS UNITS 1 & 3. 2.) SEAL HOLES IN SUPPLY DUCT WHERE SMOKE DETECTOR WERE REMOVED. 3.) LABEL AIR HANDLERS W/UNIT NUMBER. 4.) UNIT #1 NEEDS MORE INSULATION ON SUCTION LINE. 5.) MARK DATA PLATES ON AIR HANDLERS W/PROPER HEAT KIT INSTALLED. BE SURE OVER CURRENT PROTECTION CORRSPONDS W//DATA PLATE. WILL CHECK ON FINAL. OK FOR PARTIAL CEILING TILES |
| 06/05/2002 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE ADEQUATE ACCESS FOR SERVICE ON AIR HANDLERS. 2.) RELOCATEDUCT SMOKE DETECTORS TO THE RETURN AS PER 2000 IMC. RECALL FOR INSPECTION. |