Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM01658
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/29/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
07/29/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*SEE LAST INSP. WRITE UP. | |
07/25/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES DISC SW ON ROOF FOR COND. UNIT. TO HAVE WORKING CLEARANCE OF 36" IN FRONT PER 110-26 NEC. | |
07/10/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* CONDENSER OH ROOF NOT CONNECTED YET. |