Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2003 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection 0000* | |
| 01/21/2003 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection 0999*1.) 1" YARDWATER REQUIRED BY PLAN MEANS ALL THE WAY TO THE METER. YOU MAY NOT RUN 3/4" FROM METER 3 OR 4 FEET, INCREASE TO 1" AND THEN REDUCE AGAIN TO 3/4 BEFORE UNIT. 2.) MECHANICAL ROOM LOCKED NEED TO SEE ALL THE GAS PIPING. |
|
| 01/09/2003 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection 0999*1.) SEWER/HCS APPROVED ON 1/7/03 BY R MYERS OK TO BACKFILL 2.) NO CHANGE IN YARDWATER PIPING. NOT INSTALLED PER PLAN. PLAN STILL NOTE THAT YARD WATER PIPING BE 1" PVC. 3.) CONTRACTOR TO PAY RE-INSPECTION FEE. |
|
| 01/02/2003 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection 0999*1.) NO WATER TEST ON SEWER LINE 2.) WATER NOT INSTALLED PER APPROVED PLAN. |