Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/25/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 09/20/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999$USED #14 AWG CU. PIGTAILS FOR 20AMP KITCHEN CIRCUITS. A REINSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION. |
| 09/17/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*DENIED NO MESSAGE. SPOKE TO OWNER 8-28-02. TOLD HIM NEEDED LETTERHEAD FROM LICENSED EL.CONTR. DOING WORK AND ACCEPTING, NEED FAX, CONTRACTOR DOING WORK ONLY HAS REMODEL REPAIR LICENSE. NO INSPECTION |
| 09/13/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
DENIED NO MESSAGE NO HOME NEED LETTERHEAD CONTRACTOR |
| 08/28/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) NEED LETTERHEAD FROM LICENSED ELECTRICAL CONTRACTOR DOING WORK 2.) ROMEX SHEATH IS RN TOO EXCESSIVE INTO BOXER. 3.) NO METALIC SCREWS INTO PLASTIC BOXER. 4.) NEED GROUND TAIL INCORPORATED INTO MAKE UP TO RUN WITH SWITCH WIRER. |