Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/15/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 03/12/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999* 1.) PLANS INDICATE WIRING TO BE IN APPROVED RACEWAY (NO ROMEX.) 2.) ALL RELOCATED FIXTURES IN RESTROOM AREAS NOW HAVE TO BE BOLTED OR SCREWED TO T-BAR AND HAVE SIEMIC TIES TO STRUCTURAL CEILING. 3.) ONE J-BOX IN CIELING ABOVE RESTROOMS MISSING COVER, ONE CUT IN BOX AT TOILET (WOMENS) GROUND NOT TIED TO BOX 4.) MC CABLE AT OFFICE HANGING OUT OF WALL TO BE TIED OR DEAD END. |
| 02/21/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |