Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02BU02234
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*APPROVED PLAN WAS ON SITE. | |
09/27/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) INSTALL BOND BUSHING AT J-BOX TERMINATION OF 1/2" CONDUIT OUTSIDE BLD. 2.) INSTALL SEALOFF FITTING WITHIN 18" OF MOTOR TERMINATION BOX. 3.) PROVIDE FLEXABLE CONNECTION TO PUMP. MOTOR. 4.) PLANS/PERMIT NOT ON SITE. 5.) OK UG ACROSS PARKING 6.) WIRING METHODS TO COMPLY WITH 501 NEC. |