Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*APPROVED PLAN WAS ON SITE. |
| 09/27/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL BOND BUSHING AT J-BOX TERMINATION OF 1/2" CONDUIT OUTSIDE BLD. 2.) INSTALL SEALOFF FITTING WITHIN 18" OF MOTOR TERMINATION BOX. 3.) PROVIDE FLEXABLE CONNECTION TO PUMP. MOTOR. 4.) PLANS/PERMIT NOT ON SITE. 5.) OK UG ACROSS PARKING 6.) WIRING METHODS TO COMPLY WITH 501 NEC. |