Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/30/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*APPROVED PLAN WAS ON SITE.
09/27/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) INSTALL BOND BUSHING AT J-BOX TERMINATION OF 1/2" CONDUIT OUTSIDE BLD. 2.) INSTALL SEALOFF FITTING WITHIN 18" OF MOTOR TERMINATION BOX. 3.) PROVIDE FLEXABLE CONNECTION TO PUMP. MOTOR. 4.) PLANS/PERMIT NOT ON SITE. 5.) OK UG ACROSS PARKING 6.) WIRING METHODS TO COMPLY WITH 501 NEC.