Inspection History Details
Inspection Status: Correction Required
Inspection History: INITIAL CODE VIOLATION
Case Number - T01VL03131
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2001 | INITIAL CODE VIOLATION | Correction Required | EMERGENCY CALL OUT OK TO RE ENERGISE ONCE ELECTRICAL K-11 OR C-11 CONTRACTOR HAS MADE SAFE. CORRECTION AND DAMAGE REPAIR TO WIRING AS FOLLOWS. 1.) ROMEX WIRE CUT AT TOP OF ROOF JOIST. MAKE PROPER ACCESIBLE REPAIR AND REMOVE ROMEX FROM TOP OF ROOF JOIST (UNPROTECTED FROM SUBJECT PHYSICAL DAMAGE.) 2.) JUNCTION BOX IN HALLWAY MUST BE MADE ACESSIBLE BY ANY CODE MEANS 3.) IMPROPER SINGLE CONDUCTOR WIRING OF EXIST FLUORESCENT FIXTURE ABOVE CEILING NOT USED PLEASE DISCONNECT AT SOURCE. 4.) ELECTRICAL CONTRACTOR TO OBTAIN A 1HR. ELECTRICAL REPAIR PERMIT AND CALL FOR FINAL. FU. 1/4/02 |