Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: INITIAL CODE VIOLATION
| Date |
Description |
Inspector |
Results |
Comments |
| 03/16/2009 |
INITIAL CODE VIOLATION |
|
Approved |
|
| 08/17/2001 |
INITIAL CODE VIOLATION |
|
Violation |
NOTICE OF VIOLATION UNSAFE CONDITIONS 1.) DOUBLE LUGGING OF CONDUCTORS UNDER TEMANALS 2.) NO FUSE PROTECTION FOR CONDUCTORS 3.) IMPROPER CLEARENCE OF LUGS TO ENCLOUSER DUCT TAPE INSULATION NOT ALLOWED. 4.) COMBUSTIBLE MATERIAL INSIDE DISCONNECT 5.) DISCONNECT IN POOR SHAPE. 6.) ENTRANCE CONDUCTOR IN CONTACT WITH METAL PORCH OVERHEAD CLEARENCES NOT TO CODE. 7.) NEED GENERAL REPAIR PERMIT TO REPAIR PORCH 8.) EXPOSED ROMEX WIRING. SENT N.O.V. ON 8/21/01 RECEIVE CERTIFIED 8/24/01 FU. 9/21/01 |