Case: T01VL02233

Parcel: 107131280


Addresses:

2614 N BALBOA AV

Inspection Status: Correction Required

Inspection History: FOLLOW UP CODE VIOLATION

Date Description Inspector Results Comments
09/23/2004 FOLLOW UP CODE VIOLATION Correction Required SITE INSPECTION WAS DONE TODAY WHILE WITH T.P.D UNDER WARRENT TO INSPECT ALL 5 UNITS INCLUDING THE NOV WRITTEN BEFORE AND ANY NEW HOUSING ISSUES CURRENT. THE FOLLOWING ITEMS WHER FOUND IN THESE UNITS INSPECTED BY INSPECTOR CRAIG, UNITS C-D-E.
09/02/2004 FOLLOW UP CODE VIOLATION Correction Required WE MET AT CITY COURT TO MEET WITH PROSECUTOR STACY, AND TO GO OVER ISSUES FROM SITE VISIT ON BALBOA. INSP. HURD, FIRE INSP. D'ORIA, AND INSP. 2 RICK S.AT A LATER DATE THE REINSPECTION WILL BE DONE AFTER THE WARRENT IS SECURED.
08/31/2004 FOLLOW UP CODE VIOLATION Correction Required 8/31/04, VISITED SITE, INSP. CRAIG ASST.
UPON ARRIVAL MR. PUTZI WAS ON SITE, TALKED WITH MR PUTZI WHO STATED THAT HE HAS PAPER WORK FROM COURTS WITH 7 ITEMS HE IS RESPONSIBLE FOR, AND THIS IS ALL TO BE INSPECTED, NO GENERAL INSPECTION, OR INSPECTION USING NOTICE AND ORDER THAT HAS ALL READY BEEN ISSUED, ONLY THE 7 ITEMS WHICH MR PUTZI SHOWED, UNIT A, COUNT 3, UNIT B, COUNT 6, UNIT C, COUNT 9,10,11, UNIT E, COUNT 13,14,. INSP. CRAIG CALLED INSP. 2 RICK, WITH INSTRUCTION TO CALL T.P.D. TO PRESERVE THE PEACE, THIS WAS DONE, OFFICER KAREN MAST, CASE NUMBER 0408310283, ARRIVED ON SITE TALKED WITH BOTH PARTIES, AT THIS TIME MYSELF AND INSPECTOR CRAIG TALKED WITH ALL OCCUPANTS, AT THIS TIME WE WERE REFUSED ANY ENTRIES TO DO INTERIOR INSPECTIONS. ON FRIDAY 8/27/04 WE HAD CONFIRMATION FROM ALL RESIDENTS THAT YES WE COULD DO INTERIOR INSP. ON TUESDAY 8/31/04, MR PUTZI HAD TALKED WITH THEM PREVIOUSLY AND HAD THEM NOT ALLOW US ENTRY AT THIS TIME. OFFICER MAST STATED THAT WITH OUR PAPER WORK AND MR PUTZI'S SHE CAN NOT DO ANY THING FOR ENTRIES AND THAT SHE IS THERE TO RESERVE THE PEACE, OFFICER MAST DID CALL OUT A SUPERVISIOR TO EXPLAIN ISSUES. INSP. 2 RICK REQUESTED FOR US TO SITE, AS LEAVING SITE MR. PUTZI STOPED MYSELF AND INSP. CRAIG AND STATED THAT HE JUST GOT OFF THE PHONE WITH HIS LAYWER AND THAT IF WE RETURN WITH A WARRENT THAT HE WOULD NOT FIGHT THE WARRENT BUT WOULD QUASH ALL FINDINGS IN COURT. LEFT SITE.
08/31/2004 FOLLOW UP CODE VIOLATION Correction Required SITE VISIT TODAY FOR SABER FOLLOW-UP PER C-2 WAS CONDUCTED BY INSPECTOR JESS CRAIG AND JIM HURD.
AT SITE INSPECTOR CRAIG FOUND THAT THE OWNER OF PROPERTY WAS AT SITE MAKING REPAIRS TO UNIT C CONCERNING SOME LUMBER REPAIRS OF SOME SORT, THERE WAS ALSO A CLEAN-UP TEAM AT SITE REMOVING JUNK AND TRASH OFF OF LOTS.
THE OWNER STATED HE WOULD ONLY ALLOW AN INSPECTION ON A LIST OF ISSUE'S GIVEN BY C.O.T COURTS.
I DID STATE TO THE OWNER THAT THOSE ISSUE'S ARE ISSUE'S THAT NEED TO BE CLEARED UP WITH MIKE ANDERSAN OF CITY COURTS AND THAT WE ARE HERE TO DO A GENERAL INSPECTION AND FOLLOW-UP TO THE NOTICE.THE OWNER AT THIS TIME DOES NOT WANT DNR ON THE PROPERTY WITH PROPER PAPER WORK FROM THE CITY COURTS AND OR A WARRENT.
MORE NOTES ARE PENDING, WARRENT IS PENDING.
SUPERVISORS ARE AWARE OF ISSUE'S.
SITE MANAGER IS CASS---270-7914
AT SITE T.PD WILL REQUIRE A WARRENT VERY CLEAR ON WHAT DNR WANTS TO INSPECT AND WHERE AND WHAT.
08/27/2004 FOLLOW UP CODE VIOLATION Correction Required 8/27/04, ALL UNITS:
REVISITED SITE WITH INSP. J.CRAIG, TALKED WITH ALL RESIDENTS ON SITE, EXPLAINED TO ALL RESIDENTS THAT WE WOULD BE COMMING BACK ON TUESDAY 8/31/04 TO DO REINSPECTION OF INTERIORS AND EXTERIOR FROM NOTICE AND ORDER THAT HAD ALL READY BEEN ISSUED, ALL RESIDENTS AGREED AND WILL BE HOME.
FROM LOOKING AROUND WHEN TALKING WITH RESIDENTS PROPERTY STILL LOOKS DISTRESSED.
08/27/2004 FOLLOW UP CODE VIOLATION Correction Required QUICK NOTE , INSPECTOR CRAIG FOUND A HOMELESS PERSON ON THE SIDE OF UNIT C, THE TENANT FROM UNIT D WAS GIVING FOOD TO THE PERSON.
THE HOMELESS PERSON DID WAKE AND GO INTO UNIT D TO EAT HIS FOOD, THIS PERSON WAS SLEEPING IN THE SIDE YARD OF UNIT C.
12/05/2002 FOLLOW UP CODE VIOLATION Correction Required STATUS:
STILL IN COURT. WILL PLACE PACKET ON 60-DAY FOLLOW UP IN ORDER TO FILE PACKET.
11/04/2002 FOLLOW UP CODE VIOLATION Correction Required CASE STILL IN COURT. F/U IN 30 DAYS.
10/22/2002 FOLLOW UP CODE VIOLATION Correction Required CASE STILL IN APPEAL BY OWNER. RETURN PACKET IN 30 DAYS.
09/20/2002 FOLLOW UP CODE VIOLATION Correction Required STATUS:
PACKET RETURNED TO RICK. CASE MOVING TO SUPRERIOR COURT. WILL PUT PACKET ON F.U. FOR REVIEW ON 10/22/02.
08/26/2002 FOLLOW UP CODE VIOLATION Correction Required STATUS:
PACKET CAME BACK TO RICK SALDATE. MIKE RANKIN STILL ADDRESSING ISSUE OF APPEAL TO HIGHER COURT. ACTION: WILL PUT PACKET ON 15-DAY FOLLOW UP.
07/22/2002 FOLLOW UP CODE VIOLATION Correction Required COURT STATUS:
MR. PUTZI HAS APPEALED TO HIGHER COURT. CASE ON HOLD UNTIL FURTHER DIRECTION FROM PROSECUTOR'S OFFICE.
07/03/2002 FOLLOW UP CODE VIOLATION Correction Required FOLLOW UP INSPECTION:
GROUP INSPECTION CONSISTING OF RICK S, RICHARD V, GLENN D, RICK M AND MARTIN R.
INSPECTION WAS ONLY OF EXTERIOR OF UNITS. NOTE: THE OCCUPANTS OF UNIT "C" WERE VISITING UNIT "E" AND BOTH SETS OF OCCUPANTS STATED THAT THEY WOULD NOT ALLOW ENTRY UNLESS THE CITY HAD A WARRANT IN HAND.

UNITS: A & C, FOUND NO ONE HOME. LEFT NOTIFICATION OF INSPECTIONS POSTED.
UNIT A, STILL CONTAINED ADDITION IN PLACE.

UNIT: B, VACANT AND USECURED AT REAR AND WEST WINDOWS.

UNIT: D, WAS NOT ON NOTICE DUE TO VACANT AT TIME OF ORIGINAL INSPECTION BUT IS NOW OCCUPIED.

UNIT: E, OCCUPANT DENIED ENTRY, REQUESTING WARRANT.

STATUS OF VIOLATION NUMBERS ON CIVIL COMPLAINT:
#1. ADDITION STILL IN PLACE WITH NO INPECTIONS ON GENERAL REPAIR PERMIT T02CM02028. ALL OTHER VIOLATIONS ARE LOCATED IN THE INTERIOR.
#2. STILL IN VIOLATION DUE TO PERMIT DOES NOT HAVE ANY INSPECTIONS. UNABLE TO SEE HEATER.
#3. STILL IN VIOLATION DUE TO PERMIT DOES NOT HAVE INSPECTIONS.
#4. COURT DID NOT FIND VIOLATION.
#5. STILL IN VIOLATION DUE TO NO INSPECTIONS ON ASSOCIATED PERMIT. THIS UNIT IS VACANT. SOME VIOLATIONS LOCATED ON INTERIOR OF STRUCTURE.
#6. COMPLIANCE. THIS IS THE UNIT THAT IS OPEN TO UNAUTHORIZED ENTRY AT TWO WINDOWS.
#7. STILL IN VIOLATION DUE TO NO INSPECTIONS ASSOCITATED WITH PERMIT. HEATER VIOLATION IS LOCATED ON THE INTERIOR OF UNIT.
#8. STILL IN VIOLATION DUE TO NO INSPECTIONS.
#9. COMPLIANCE.
#10. STILL IN VIOLATION DUE TO NO INSPECTIONS ASSOCIATED WITH PERMITS. VIOLATIONS LOCATED IN THE INTERIOR.
#11. STILL IN VIOLATIONS DUE TO NO INSPECTIONS ASSOCIATED WITH PERMIT. VIOLATIONS LOCATED ON THE INTERIOR OF UNIT.
#12. STILL IN VIOLATION DUE TO NO INSPECTIONS ASSOCIATED WITH PERMIT. PORCH HAS BEEN WORKED ON BUT IS LOCATED TO CLOSE TO PROPERTY LINE.
#13. UNABLE TO GAIN ENTRY AND VIOLATIONS LOCATED ON THE INTERIOR.
#14. UNABLE TO GAIN ENTRY AND VIOLATION LOCATED ON THE INTERIOR.

NOTE: PERMITS FOUND IN PERMITS PLUS ARE IN ISSUED STATUS BUT NO INSPECTIONS ASSOCIATED AT ALL. NUMBERS ARE AS FOLLOWS.
* UNIT-A: T02CM02028.
* UNIT-B: T02CM02029
* UNIT-C: T02CM02030
* UNIT-E: T02CM02031
04/19/2002 FOLLOW UP CODE VIOLATION Correction Required WENT TO COURT FOR DAY #2 ON SABER CASE.
04/05/2002 FOLLOW UP CODE VIOLATION Correction Required WENT TO COURT ON SABER CASE. HAVE NEW COURT DATE 4/19/02 TO CONTINUE SAME CASE.
04/04/2002 FOLLOW UP CODE VIOLATION Correction Required SABER CASE CONTINUES TO MOVE FORWARD. OWNER WORKING WITH DSD AND PROSECUTOR'S OFFICE. ACTION FU 60 DAYS.
01/11/2002 FOLLOW UP CODE VIOLATION Correction Required PERMIT INFO UPDATE: AS OF 1/11/2 THE COMPUTER SHOWS TWO PERMITS FOR UNIT-A BOTH OF WHICH ARE IN WALKTHRU STATUS. T01CM04457 IS A GENERAL REPAIR AND WAS SUBMITTED ON 9/10/01. T01CM05649 IS FOR AN ADDTION AND IS ALSO IN WALKTHRU STATUS, APPLIED 11/16/01.
12/06/2001 FOLLOW UP CODE VIOLATION Correction Required FOLLOW UP INSPECTION:
NOTE: NUMBERS CORRESPOND TO ORIGINAL N & O.

A) UNIT-A: (1) ADDITION ON EAST SIDE HAS NOT BEEN ADDRESSED. CIELING IN LIVING ROOM HAS BEEN REPLACED WITH ELECTRICAL REMOVED IE; RECESSED LIGHTING AND FAN. ELECTRICAL IN BEDROOM HAS BEEN REMOVED. ELECTRICAL SUPPLYFROM MAIN SERVICE HAS NOT BEEN PERMITTED, BUT OWNER IS WORKING ON. WALL HEATER HAS NO PERMITS ACCORDING TO COMPUTER BUT NOW WORKS. (2) CIELINGS, INTERIOR AND EXTERIOR HOLES HAVE BEEN SEALED. TENANT RELAYED THAT STRUCTURE DID NOT LEAK ON RECENT RAINS. FRONT DOOR WEATHER PROTECTION VIOLATION REMOVED PER APPEAL BY OWNER. BROKEN WINDOW REPAIRED. ADDITION HAS NOT BEEN ADDRESSED. (3) HEATER IS WORKING BUT NO PERMIT PULLED. (4) GENERAL DILAPIDATION ISSUES REPAIRED. KITCHEN SINK WAS MISSING DURING INSEPCTION BUT WAS DUE TO REPLACING. (5) EXPOSED WIRES IN CIELING REMOVED AS WELL AS CONDUIT. COVER PLATES REPLACED, NOT PERMITS NECESSARY DUE TO REMOVAL. (6) OFFICE ELECTRICAL ISSUES HAVE BEEN CORRECTED. (7) CONDUIT HAS BEEN RECONNECTED BUT STILL NOT PERMITTED. BLANK COVERS FOR LACKING BREAKERS IN SERVICE PANEL STILL MISSING. INTERIOR ELECTRICAL WORK HAS BEEN REMOVED. EXTERIOR OUTLETS ISSUE HAS BEEN ADDRESSED BY REMOVING ONE AND INSTALLING A WEATHER PRTECTED COVER ON THE OTHER. (8) CIELING REPAIRED AND ILLEGAL WIRING REMOVED. (9) APPEAL GRANTED. (10) BATHROOM WINDOW STILL DOES NOT FUNCTION FOR VENTILATION. (11) VIOLATION ABATED- DOORS HAVE BEEN CORRECTED FOR EXITING. (12) ABATED- SMOKE DETECTORS INSTALLED.

ADDITIONAL VIOLATIONS: THE WALL HEATER, ALTHOUGH NOW OPERABLE, WAS INSTALLED W/O PERMITS. THE OWNER CLAIMS THAT IT IS ORIGINAL BUT THE INITIAL INSPECTION FOUND RECENT WORK AS IF BEING INSTALLED. THE TENANT ALS0 STATED THAT IT WAS A REPLACEMENT HEATER. THE OTHER UNITS HAVE THIER HEATERS LOCATED IN THE HALL WAYS. UNIT-A's HEATER LOCATION DOES NOT ALLOW FOR THE OTHER HABITAL ROOMS SUCH AS THE 2ND BEDROOM, KITHCHEN AND LIVING ROOM TO BE PROPERLY HEATED. THE FACIA ON THE ROOF WAS REPLACED AND THE EDGING WHICH KEEPS WATER OUT WAS NOT REPLACED. THE MAIN ELECTRICAL SERVICE DOES NOT HAVE THE CIRCUITS LABELED IN CASE OF SHUT OFF. THE KITCHEN LACKS A GFCI RECEPTICLE NEAR THE SINK AREAS. THIS IS NOW NECESSARY DUE TO THE LARGE AMOUNTS OF REMODEL AND ELECTRICAL WORK.

B) UNIT-B: (13) VIOLATION ABATED IN THAT PLYWOOD HAS BEEN REPLACED AND A 4 X 4 POST HAS BEEN INSTALLED AS A SUPPORT. NOTE, WOOD HAS NOT BEEN PAINTED AND WILL RESULT IN THE DETERIORATION AT A FAST PACE RESULTING IN THE SAME SITUATION. (14) VIOLATION ABATED, OPENING CLOSED OFF. (15) VIOLATIONS NOT ABATED. GAS LINES STILL IN PLACE, HEAT NOT OPERATIVE, CLOSET ADDITION STILL IN PLACE, SUB PANEL STILL NOT PERMITED. (16) VIOLATION NOT ABATED, IN ADDITION TO SMALLER WINDOWS THE TENANT ALSO HAS AN A/C UNIT IN ONE OF THE WINDOWS.

NOTE: ADDITONAL VIOLATIONS SUCH AS ROOF EDGING LACKING DUE TO CHANGE OF FACIA. SEWER VENT DETERIORATED AND NOW DOES NOT EXTEND PAST THE ROOF FOR PROPER SEWER OPERATION AND TO DISBURSE GAS IN SAFE MANNER.

C) UNIT-C: (17) VIOLATION NOT IN COMPLIANCE. ELECTRICAL STILL NOT RESOLVED, CLOSET ADDTION STILL NOT PERMITTED. WALL HEATER STILL NOT PERMITTED. (18) VIOLATION APPEALED AND GRANTED. (19) SMOKE DETECTORS INSTALLED. (20) ALL VIOLATIONS RE GENERAL DILAPIDATION ABATED. (21) VIOLATION APPEALED AND GRANTED. (22) OWNER HAS PATCHED CRACK BUT CONTRACTOR WAS NOT OBTAINED TO ASSESS STRUCTURAL INTEGRITY. (23) VIOLATION ABATED. CIELINGS HAVE BEEN REPAIRED. (24) VIOLATION NOT ABATED. WINDOW COVERSION TO SMALLER WINDOW HAS NOT BEEN ADDRESSED. OWNER MUST APPEAL TFD AND DSD, LIFE SAFETY ISSUE. (25) VIOLATION NOT ABATED. HAZARDOUS ELECTRICAL HS NOT BEEN ADDRESSED. (26) VIOLATION NOT ABATED. THE UNION LOCATED INSIDE THE HOUSE HAS BEEN ELIMINATED BUT THE FLEX LINE WHICH PENETRATES THE WALL HAS NOT BEEN ADDRESSED.

NEW VIOLATION; THE ROOF EDGING IS LACKING DUE TO THE REPLACEMENT OF THE FACIA.

D) UNIT-D: THE UNIT APPEARS TO BE OCCUPIED AS INDICATED BY THE NIEGHBORS BUT NO ONE WAS HOME. LETTER LEFT ON DOOR RE INSPECTION.

E) UNIT-E: (28) VIOLATION NOT ABATED. THE OWNER ATTEMPTED TO STABILIZE THE PORCH BY REPLACING STRUCTURAL MEMBERS WHICH AGAIN REQUIRE PERMITS. THE PORCH SHOULD BE EITHER REMOVED OR PERMITTED. THE GAS LINES AND THE WATER HEATER, STILL HAVE NOT BEEN PERMITTED. (29) VIOLATION ABATED. COOLING FIXED. (30) VIOLATION APPEALED AND GRANTED. (31) VIOLATION NOT ABATED. EXTENSION CORDS STILL BEING USED AND LIGHT FIXTURE STILL NOT FIXED. (32) VIOLATION NOT ABATED, NO SMOKE DETECTORS. (33) VIOLATION ABATED. (34) VIOLATION ABATED RE GENERAL DILAPIDATION.
08/02/2001 FOLLOW UP CODE VIOLATION Correction Required VIOLATIONS SUMMARY:

Unit A:
A) UHC 301: Work w/o permits re (1) addition located on the east side of the structure, used as storage and office space. Contains electrical circuits some being in a hazardous condition. (2) Remodel of living room in that ceiling has been removed with the installation of electrical wiring to power recessed lighting and an electrical fan. (3) Bedroom contains electrical in conduit running along the east wall. (4) Electrical supply to unit from main service appears to have been recently installed with work extensive enough to have required city permits. Records located at Development Services do not show permits. (5) The wall heater has recently been replaced without permits in the office.
CITY REQUIREMENTS: A licensed electrical contractor will be required to review all electrical work installed w/o permits. A permit(s) will be required for all work installed and corrections made for any deficiences found. The heater must be permitted with the proper heating requirents met by housing codes.
B) UHC 601.2: Interior and exterior structure contained holes, the ceiling showed signs of leaking all from deterioration & lack of maintenance. The front door was not sealed properly, the living room window was broken and the addition was not sealed properly thus the unit lacked proper weather protection.
CITY REQUIREMENTS: Propvide proper weatherization. Make repairs and secure permits if required.
C) UHC 701.1: The wall heater was replaced thus the owner must now comply with the housing code that states that all habital rooms must be heated to 70 degrees F, at least 3'-above the floor.
CITY REQUIREMENTS: Proper heating must be provided and permits must be secured for the installation of the heating equipment.
D) UHC 901: lacking smoke detectors
E) UHC 1001.2(13): General dilapidation & lack of maintenance: Holes in the ceilings and walls, a bedroom door was missing, the living room window was broken. The kitchen was found with a deteriorated ceiling, broken light switch and a leaking sink.The bathroom was found with a leaking sink, a cold water shut off not working properly and a deteriorated shower stall. Poor workmanship in repairs and extensive amounts of improvements understaken with out permits have resulted in unfinished ceiling, exposed wires, unsealed weather protection.
CITY REQUIREMENTS: Repair all dilapidated conditions. Secure required permits.
F) UHC 1001.5: Hazardous Electrical: Exposed wires in the living room, unfinished ceiling. Unsupported electrical conduit, Incorrect electrical boxes in the office, open grounds in recepticles, possibly due to unpermited work, missing cover plates, broken switches, open junction boxes in the living room ceiling, exterior south wall and exterior conduit which was never inspected resulting in separation which has exposed wires. Blank covers at breakers in main service missing and extensive amounts of illegal electrical work performed on the interior and exterior.
CITY REQUIREMENT: Peform electrical corrections and repairs. Secure all necessary permits.

Unit B:

A) DBC 302(5) : The cooler is in danger of collapsing in that the plywood support is severly warped to the point of failure.
CITY REQUIREMENT: Provide secure support for the cooler.

B) UHC 301: Work W/O permits re (1) Plumbing - a gas line was found feeding the heater and stove. Line crosses a bedroom door entrance along floor. Water heater was installed w/o permits. (2) Structual - the front porch has an additon used to provide a closet to the bedroom. (3) The structure has had electrical work as evidenced from recepticles found in the bedroom which are three wire while the structure contains 2-wire recepticles. The exterior structure contains a sub-panel, conduit and electrical wiring which is part of a master meter system.
CITY REQUIREMENTS: Secure permits for required plumbing, structual and electrical work.

C) UHC 601.2 : Lack of weather protection: in that the structure contains an old evaporative cooler which has been re-located with the vent opening stuffed with a pillow. The front door does not seal properly.
CITY REQUIREMENT: Provide proper weatherization for the unit.
D) UHC 1001.12: The the bedroom windows have been replaced with smaller sized than originally installed. This is in violation of the UBC 310.4 which was in effect at the time of construction of the structure.
CITY REQUIREMENTS: Replace windows with proper sized windows.

Unit C:

A) UHC 301: Work w/o permits:(1) the electrical supply has been replaced by added sub-panels, conduit and wiring on the exterior connected to the main master meter.(2) Structual, a small exterior addition has been added and is being used as a closet for the bedroom.
CITY REQUIREMENTS: Secure plans & permits to address or remove.
B) UHC 601.2: The structure is not sealed from the elements in that the wall on the east side is badly cracked, doors and windows are not sealed.
CITY REQUIREMENTS: Seal doors & windows from the elements. Address structual cracks.
C) UHC 901: The structure is lacking smoke detectors.
CITY REQUIREMENT; Install smoke detectors.
D) UHC 1001.2(5,13): General dilapidation: The structure contains deteriorated ceilings(kitchen,bedroom & bathroom), walls, electrical fixtures(light, switches,bathroom counter sink, holes in walls and repairs of poor workmanship (bathroom light fixture,furnace gas line, pillow to seal vent opening of relocated cooler, and romex wire located behind the refrigerator). The kitchen sink is leaking at the trap and the shower surround is heavily deteriorated. The fixtures lacked hot water at the time of inspection.
CITY REQUIREMENT: Make repairs and corrections. Secure required permits.
E) UHC 1001.3(4): The unit showed structural cracks of approximately 3 inches penetrating from the exterior to the interior on three of the four sides.
CITY REQUIREMENTS: Secure a licensed contractor to verify structural integrity of the building. Owner to make repairs based on the recommendations. Permits secured as required.
F) UHC 1001.5: The light fixture in the bathroom is is not properly installed, recepticles have not been wired correctly and show open grounds when tested. There is excessive use of extension cords, including power to the evaporative cooler .
G) UHC 1001.6: Hazardous plumbing: The gas line has been repaired in a hazardous manner in that a union was located in the interior, behind the stove. A repair has been made to the gas line feeding the wall furnace, connecting the buried gas line with flex line into the wall.
CITY REQUIREMENT: Properly make repairs as per the plumbing code.
G) UHC 1001.8(2): Doors, windows, roof and east wall do not provide for proper weather protection.
CITY REQUIREMENT: Provide proper weatherization. Secure required permits.
H) UHC 1001.12: The bedroom windows have been replaced with smaller windows hampering emergency escape.
CITY REQUIREMENT: Replace original window size or comply with 1994 edi, UBC sect 310.4.

Unit D & E:
Note: although unit D is vacant, they share plumbing and electrical and this covers both.
A) UHC 301.:(1) The rear porch has been built w/o permits and is currently collapsing due overspanned rafters & undersized beams. (2) Gas lines have been added or repaired incorrectly, evidenced by improper placement of the union and shut off valve located at the rear of the structure. This does not allow for proper shut off from the meter. (3) The water heater has been replaced w/o permits. (4) electrical improvements have been made to this unit as with others improperly and without permits.
CITY REQUIREMENT: Make repairs and corrections. Secure required permits..
B) UHC 601.2: Weather protection:a crack in the kitchen (east wall), roof leaks in the living room and a front door which is heavily deteriorated do not provide for proper weather protection.
CITY REQUIREMENTS: Provide proper weatherization of structure. Secure permits as required.
C) UHC 701.3: The cooler does not not operate.
CITY REQUIREMENT: Repair cooler.
D) UHC 901 : The unit lacks a smoke detector.
CITY REQUIREMENT: install smoke detector.
E) UHC 1001.1(13): general dilapidation in that (1) the kitchen has the counter top disattaching, faucets missing,cabinets deteriorating (surround, cabinet walls, sink not sealed), heavy peeling paint and flooring missing. (2) The living room has switches missing by the bathroom, window cranks missing and the front door and the front door frame is badily deteriorated. (3) The bathroom contains a leaking toilet, windows that do not open due to lack of window cranks, and a door that does not close properly.
CITY REQUIREMENTS: Make necessary repairs. Secure required permits.
07/27/2001 FOLLOW UP CODE VIOLATION Correction Required 3RD inspection History
Inspections were conducted by Richard V., Glenn D., Ceci Cruz & Mike Rankin with TPD serving warrant. Entry was gained for unit C with the decision made not to enter unit D.
07/26/2001 FOLLOW UP CODE VIOLATION Correction Required 2ND inspection: History

Inspections were conducted by Rick Saldate & Richard Vidal of DSD, and Glenn D'Auria of TFD with warrant served by TPD. Complete inspections were conducted to units A & E. Maint man served on site inspectors with paperwork re our inspection intent. Paperwork reviewed by Prosecutor's Office with contact to associated attny conducted. Inspection proceeded with unit C to be attempted next day in order to allow occupant to be present. Unit E, was not locked and inspections were conducted. TPD was [resent the entire time.