Permit: T01PL02439

Parcel: 110063940


Addresses:

3024 N DESERT DR

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/04/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST REMOVE UNION IN LINE ON ROOF AND REPLACE WITH RIGHT & LEFT HAND NIPPLE SEC SECTION: 1211.10 94 UPC. 2.) MUST USE (3) SHEET METAL SCREWS @ VENT COLLAR AND JOINTS FOR WATER HTR FLU VENT 3.) RETEST SYSTEM 10LBS MIN.
12/04/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT & CAP, P & T. VALVE & DRAIN IS OK 4.) FURNACE IS GAS PACK ON ROOF OK 5.) U.C.C. HAS BEEN PLACED @ METER LOCATION.