Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/04/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST REMOVE UNION IN LINE ON ROOF AND REPLACE WITH RIGHT & LEFT HAND NIPPLE SEC SECTION: 1211.10 94 UPC. 2.) MUST USE (3) SHEET METAL SCREWS @ VENT COLLAR AND JOINTS FOR WATER HTR FLU VENT 3.) RETEST SYSTEM 10LBS MIN. |
| 12/04/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT & CAP, P & T. VALVE & DRAIN IS OK 4.) FURNACE IS GAS PACK ON ROOF OK 5.) U.C.C. HAS BEEN PLACED @ METER LOCATION. |