Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/04/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST REMOVE UNION IN LINE ON ROOF AND REPLACE WITH RIGHT & LEFT HAND NIPPLE SEC SECTION: 1211.10 94 UPC. 2.) MUST USE (3) SHEET METAL SCREWS @ VENT COLLAR AND JOINTS FOR WATER HTR FLU VENT 3.) RETEST SYSTEM 10LBS MIN. |
| 12/04/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT & CAP, P & T. VALVE & DRAIN IS OK 4.) FURNACE IS GAS PACK ON ROOF OK 5.) U.C.C. HAS BEEN PLACED @ METER LOCATION. |