Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01PL00248
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
01/29/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* INCORRECT FLEX CONNECTOR YOU MUST USE ONE DESIGNED FOR CONNECTION TO A MOBILE HOME VALVE TO BE INSTALLED UPSTREAM FROM INSOLATION UNION INCORRECT PRESSURE TEST. TEST TO BE DONE WITH VALVES ON AND FLEX LINES ATTACHED AND CAPPED UNDERGROUND GAS TO BE TESTED AT 10 PSI OR MORE |