Permit: T01PL00248

Parcel: 11943001A


Addresses:

1655 W AJO WY


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T01PL00248

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
01/29/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
INCORRECT FLEX CONNECTOR YOU MUST USE ONE DESIGNED FOR CONNECTION TO A MOBILE HOME
VALVE TO BE INSTALLED UPSTREAM FROM INSOLATION UNION
INCORRECT PRESSURE TEST. TEST TO BE DONE WITH VALVES ON AND FLEX LINES ATTACHED AND CAPPED
UNDERGROUND GAS TO BE TESTED AT 10 PSI OR MORE