Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T01OT00418
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2008 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 10/02/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) ALL FITTINGS CONDUIT NIPPLES, ETC MUST BE WRENCH TIGHT. 2.) FLEX CONDUIT MUST BE SECURLY FASTENED ONTO CONDUIT NIPPLE 3.) COUPLINGS ARE NOT LISTED FOR THIS APPLICATION YOU MUST USE FEMALE CONDUIT NIPPLES ON THE ENDS OF ALL THREND PASS THROUGHS. 4.) FLEXIBLE CONDUIT IS REQUIRED TO BE SECURED WITHIN 12' OF EACH END FOR EVERY LENGTH OVER 3' IT MUST ALSO BE SECURED EVERY 3'5.) TRANSFORMER REQUIRED TO BE AS CLOSE AS POSSIBLE" TO NEON. MOUNTING IT ON WALL WOULD BE BETTER. | |
| 09/26/2001 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FULL CYCLE NEON WALL MOUNT. |