Inspection History Details
Inspection Status: Approved
Inspection History: MOBILE HOME ELECTRICAL
Permit Number - T01MH00544
Inspection Description - MOBILE HOME ELECTRICAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2001 | MOBILE HOME ELECTRICAL | Approved | IVRS - Inspection 0000* | |
| 10/23/2001 | MOBILE HOME ELECTRICAL | Partial Approval | IVRS - Inspection 0000*AT THE METER PANEL: CONNECT THE GREEN GROUND WHIRE TO THE SAME TERMINAL STRIP AS THE NEUTRAL CONDUCTOR. | |
| 10/19/2001 | MOBILE HOME ELECTRICAL | Partial Approval | IVRS - Inspection 0000*AT THE METER PANEL: INSTALL A GREEN GROUNDING CONDUCTOR FROM THE NEUTRAL TERMINAL STRIP TO THE GROUND LUG ON THE MOBILE HOME RECEPT. INSIDE PANEL: ALL GROUNDING CONDUCTORS MUST BE ON ONE STRIP OR INTERCONNECTED WITH THE PROPER SIZED WIRE. |