Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0930*1.) THE SPACE WAS FORMERLY A CATERING CONCERN WITH PROVISION FOR FOOD PREP.. THIS HAS BEEN REMOVED. 2.) SOME CHANGES/REMODEL HAVE BEEN DONE. 3.) PLEASE SUBMIT A PLAN DEPICTING. THE NEW ELECTRICAL LAYOUT AND ALL ADDITIONS MADE. 4.) SUBMIT PLAN TO THIS DEPARTMENT FOR REVIEW AND APPROVAL. 5) DO NOT DRYWALL ANY WALLS UNTIL INSPECTION, TO NEW PLAN, HAS BEEN DONE. |