Permit: T01EL02495

Parcel: 110110320


Addresses:

2657 N ARCADIA AV

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/18/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*1.) INSTALL SCREWS OR RIVITS TO HOLD ADDRESS LABEL ON SERVICE. 2.) COVER LB AT LEFT SIDE OF SERVICE 3.) NEW SERVICE INSTALLED OVER 24" PATIO WALL IN VIOLATION OF DEDICATED WORKING SPACE. 110-26 N.E.C. 4.) DO NOT SPLICE GROUNDING ELECTRODE CONDUCTOR IN GROUND ROD CLAMP. 250-50 N.E.C.