Permit: T01EL02420

Parcel: 13216600B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/13/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*1.) CADWELL SHOT ON GROUND RD IN FRONT O FMAIN SW TO BE RESHOT.
03/12/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
12/19/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) GROUND RODS 2-6' APART
4.) INSULATION ON SEC LL HAND SECTION.
SES & CONDUCTORS OK MBJ OK.
1.) SINCE THIS SWITCH GEAR WAS ONLY REPLACED NOT INCREASED OK FOR EXISTING GAS LINE TO REMAIN.
2.) 2 GROUND RODS ARE REQUIRED TO COMPLETE GROUNDING SYSTEM.
3.) HAVE INSPECTED TIE IN ON GEAR FROM TEP AND VERIFIED TERMINATION, MAIN BONDING JUMPER, REQUESTED 2 EXISTING CONDUITS TO BE RETIED TO GROUND BAR FROM BUSHINGS
4.) APPLYING INSULATION ON BOTTOMM LEFT HAND CONDUCTORS TOO NEAR FRAME.
5.) VERIFIED CHANGE FROM 1/0 GROUNDS TO NEUTRAL FOR MCC-1 & 2 ALSO 350 MCM NEUTRALS TO GROUND NEUTRAL FOR MCC-1 & 2.
CONTRACTOR HAD AN APPROVED CHANGE ON SITE.
11/07/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*