Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02420
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*1.) CADWELL SHOT ON GROUND RD IN FRONT O FMAIN SW TO BE RESHOT. | |
03/12/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
12/19/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) GROUND RODS 2-6' APART 4.) INSULATION ON SEC LL HAND SECTION. SES & CONDUCTORS OK MBJ OK. 1.) SINCE THIS SWITCH GEAR WAS ONLY REPLACED NOT INCREASED OK FOR EXISTING GAS LINE TO REMAIN. 2.) 2 GROUND RODS ARE REQUIRED TO COMPLETE GROUNDING SYSTEM. 3.) HAVE INSPECTED TIE IN ON GEAR FROM TEP AND VERIFIED TERMINATION, MAIN BONDING JUMPER, REQUESTED 2 EXISTING CONDUITS TO BE RETIED TO GROUND BAR FROM BUSHINGS 4.) APPLYING INSULATION ON BOTTOMM LEFT HAND CONDUCTORS TOO NEAR FRAME. 5.) VERIFIED CHANGE FROM 1/0 GROUNDS TO NEUTRAL FOR MCC-1 & 2 ALSO 350 MCM NEUTRALS TO GROUND NEUTRAL FOR MCC-1 & 2. CONTRACTOR HAD AN APPROVED CHANGE ON SITE. |
|
11/07/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* |