Permit: T01EL02420

Parcel: 13216600B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01EL02420

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2003 ELECTRIC - INTERMEDIATE Approved
11/07/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
09/11/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*LABEL ALL DISCONNECT PANEL BOARD MCC'S ETC. 2.) NOTE 16. NO NEUTRALS DESIGNATED AMOUNT OF NEUTRAL3.) CLEARANCE IN FRONT OF S.E.S. IMPROPER (ABOVE THE 6 1/2FT AREA.) 4.) NEED A GFI PERFORMANCE TEST. 5.) UTILTIY COMPARTMENT SEALED. NEED TO HAVE OPENED ENERGIZED W/OUT CITY CLEARANCE 6.) WILL NEED COMPANY LETTERHEAD INDICATING ALL TORQUED PER MANUFACTURE VALVES 7.) NO NEUTRAL WIRE FOR PANE L.B.? 8.) NEED GROUNDING ELECTRODE SYSTEM OPEN ALL.
07/29/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0925$NEED APPROVED PLAN AT SITE. A REINSPECTION FEE IN DUE BEFORE THE NEXT INSPECTION.
07/18/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000$SUPPORT CONDUIT W/IN 3FT OF BOXER AND VERY 10FT. THEREAFTER THANKS JERRY. WILL NEED CITY APPROVED PLANS UPON NEXT INSPECTION. PLACING PLANS AT S.W. COLUMN WILL BE APPRICATED.