Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T01EL02420
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2003 | ELECTRIC - UFER | Approved | ||
11/07/2002 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection 0000*NOT READ INSPECTION TO CONTINUE AMONG CORRECTION BELOW I WILL NEED TO CONTINUE A W/"BELOW SES IE. MCC-1 MCC 2,T-2, TRANSFER SWITCHES AND MORE. 1.) TORQUING LETTER RECEIVED OK 2.) NEED TO SEE SECONDARY TERMINATION ARRANGE W/T.E.P. AND CALL 791-5550 X 1136 FOR SCHEDULING. 3.) HEAD ROOM CLEARANCE IN FRONT OF SES IN VIOL. OF 110-26 4.) MIN GROUND SYSTEM RODS, STEEL, WITH WATER AND GAS BOND. 5.) SECODNARY CONDUCTOR CANNOTBE VERIFIED PANEL LB AND W WIRING NOT PER APPROVED PLAN 6.) MCC-2 NEED 1/0 GRND EACH. ALSO MCC-1. |