Permit: T01EL02420

Parcel: 13216600B

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
03/13/2003 ELECTRIC - UFER Approved
11/07/2002 ELECTRIC - UFER Partial Approval IVRS - Inspection 0000*NOT READ INSPECTION TO CONTINUE AMONG CORRECTION BELOW I WILL NEED TO CONTINUE A W/"BELOW SES IE. MCC-1 MCC 2,T-2, TRANSFER SWITCHES AND MORE.
1.) TORQUING LETTER RECEIVED OK
2.) NEED TO SEE SECONDARY TERMINATION ARRANGE W/T.E.P. AND CALL 791-5550 X 1136 FOR SCHEDULING. 3.) HEAD ROOM CLEARANCE IN FRONT OF SES IN VIOL. OF 110-26 4.) MIN GROUND SYSTEM RODS, STEEL, WITH WATER AND GAS BOND.
5.) SECODNARY CONDUCTOR CANNOTBE VERIFIED PANEL LB AND W WIRING NOT PER APPROVED PLAN 6.) MCC-2 NEED 1/0 GRND EACH. ALSO MCC-1.