Permit: T01EL01737

Parcel: 129023890


Addresses:

2725 E MALVERN ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) BE ADVISED: 1.) THE 1999 ELECT. CODE REQUIRES THE GAS PIPING BE GROUNDED (BOWDED) TO THE GROUNDING SYSTEM GROUND WIRE OR TO THE MAIN PANEL NEUTRAL BAR. YOU MAY AL GROUND THE GAS LINE BY CONNECTING A BONDING JUMPER FROM THE COLD WT PIPE TO THE GAS LINE AT THE WTR. HTR. REF. ART 250 NEC 1999. 2.) THE CIRCUIT BREAKERS MUST BE LABELED/MARKED WITH THE EQUIPMENT OR AREAS THEY SERVE. CORRECT & RECALL FOR FINAL APPROVAL.