Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/15/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/11/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) SEPERATE NEUTRAL AND GROUND #15 2.) NEED GROUNDING ELECTROBE SYSTEM AT EACH TRAILER PLUG CONNECTION. 3.) PLEASE PROVIDE VERIFICATION OF LISTING FOR PULL BOXES. |
| 07/10/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) INGROUND PULL BOXES TO BE LISTED AND APPROVED FOR ELECTRIAL USE.2) USE CORRECT BREAKERS SINGLE POLE FOR 110V AND 2 POLE FOR 220V 3.) USE APPROVED SPLICEING STANDARDS FOR SPLIT BOLT CONNECTION 4.) NEED PLANS AND JOB ACRD ON SITE 5.) NEED TO VERIFY./GROUNDING AT TRAILER CONNECTIONS. LEFT MESSAGE ON PHONE DIDNOT HAVE A RETURN BY TIME I LEFT INSPECTION. |
| 06/28/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0925*1.) NEED TO BOND NEUTRAL AT SERVICE 2.) NEED APPROVED PLANS AND JOB CARD ON SITE 3.) PLEASE HAVE SERVICE COMPLETE READY FOR CROSS OVER |