Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL01602
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/11/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) SEPERATE NEUTRAL AND GROUND #15 2.) NEED GROUNDING ELECTROBE SYSTEM AT EACH TRAILER PLUG CONNECTION. 3.) PLEASE PROVIDE VERIFICATION OF LISTING FOR PULL BOXES. | |
07/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) INGROUND PULL BOXES TO BE LISTED AND APPROVED FOR ELECTRIAL USE.2) USE CORRECT BREAKERS SINGLE POLE FOR 110V AND 2 POLE FOR 220V 3.) USE APPROVED SPLICEING STANDARDS FOR SPLIT BOLT CONNECTION 4.) NEED PLANS AND JOB ACRD ON SITE 5.) NEED TO VERIFY./GROUNDING AT TRAILER CONNECTIONS. LEFT MESSAGE ON PHONE DIDNOT HAVE A RETURN BY TIME I LEFT INSPECTION. | |
06/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0925*1.) NEED TO BOND NEUTRAL AT SERVICE 2.) NEED APPROVED PLANS AND JOB CARD ON SITE 3.) PLEASE HAVE SERVICE COMPLETE READY FOR CROSS OVER |