Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/19/2001 |
ELECTRIC - TEMPORARY POLE |
|
Approved |
IVRS - Inspection 0000* |
| 06/18/2001 |
ELECTRIC - TEMPORARY POLE |
|
Denied |
IVRS - Inspection 0999*1.) PERMANENTLY ID MAIN DISCON BY TRANS 2.) PRIMARY LUGE GOOD FOR #6-250 NOT #8 3.) PHASE ID SECONDARY IN TRANSFORNER.4.)60A MAIN CB IN 120/208V PANEL NEEDS A HOLD DOWN SCREW OR CLIP WHEN A CB IS BACK FED ONE IS REQUIRED. 5.) INSTALL FUSING AT METER SITION DISCONNECT |