Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/19/2001 |
ELECTRIC - TEMPORARY POLE |
|
Approved |
IVRS - Inspection 0000* |
| 06/18/2001 |
ELECTRIC - TEMPORARY POLE |
|
Denied |