Permit: T01EL01512

Parcel: 128010010

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY POLE

Date Description Inspector Results Comments
06/19/2001 ELECTRIC - TEMPORARY POLE Approved IVRS - Inspection 0000*
06/18/2001 ELECTRIC - TEMPORARY POLE Denied IVRS - Inspection 0999*1.) PERMANENTLY ID MAIN DISCON BY TRANS 2.) PRIMARY LUGE GOOD FOR #6-250 NOT #8 3.) PHASE ID SECONDARY IN TRANSFORNER.4.)60A MAIN CB IN 120/208V PANEL NEEDS A HOLD DOWN SCREW OR CLIP WHEN A CB IS BACK FED ONE IS REQUIRED. 5.) INSTALL FUSING AT METER SITION DISCONNECT