Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
Permit Number - T01EL01512
Inspection Description - ELECTRIC - TEMPORARY POLE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2001 | ELECTRIC - TEMPORARY POLE | Approved | IVRS - Inspection 0000* | |
06/18/2001 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection 0999*1.) PERMANENTLY ID MAIN DISCON BY TRANS 2.) PRIMARY LUGE GOOD FOR #6-250 NOT #8 3.) PHASE ID SECONDARY IN TRANSFORNER.4.)60A MAIN CB IN 120/208V PANEL NEEDS A HOLD DOWN SCREW OR CLIP WHEN A CB IS BACK FED ONE IS REQUIRED. 5.) INSTALL FUSING AT METER SITION DISCONNECT |