Permit: T01CM05473

Parcel: 13109203A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/13/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
05/12/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) SWITCHES TO BE GROUNDED 380-9.
2.) PLEASE REPAIR INSULATION ON CONDUCTORS AT BATH FIXTURE.
3.) #8 NM CABLE TO BE BREAKERED AS PER AMPACITIES IN CODE 336-26.
4.) GROUNDING EQUIPMENT CONDUCTORS TO BE INSTALL AS PER MANFACUTRES LABEL FOR MULTIPOLE CONDUCTORS.
5.) AN APPROVED CONNECTOR IS NEEDED AT HOOD.
6.) AN APPROVED EXTENDER RING IS NEEDED AT COMBUSTABLE IN CABINETS.
7.) PROPERLY IDENTIFY UNGROUNDED CONDUCTORS AT W/H DISCONNECT
8.) WE HAVE LOOSE SEALTITE FITTINGS AT A/C AND PROERLY SUPPORT SEAL TITE.