Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
| 05/12/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) SWITCHES TO BE GROUNDED 380-9. 2.) PLEASE REPAIR INSULATION ON CONDUCTORS AT BATH FIXTURE. 3.) #8 NM CABLE TO BE BREAKERED AS PER AMPACITIES IN CODE 336-26. 4.) GROUNDING EQUIPMENT CONDUCTORS TO BE INSTALL AS PER MANFACUTRES LABEL FOR MULTIPOLE CONDUCTORS. 5.) AN APPROVED CONNECTOR IS NEEDED AT HOOD. 6.) AN APPROVED EXTENDER RING IS NEEDED AT COMBUSTABLE IN CABINETS. 7.) PROPERLY IDENTIFY UNGROUNDED CONDUCTORS AT W/H DISCONNECT 8.) WE HAVE LOOSE SEALTITE FITTINGS AT A/C AND PROERLY SUPPORT SEAL TITE. |