Permit: T01CM05473

Parcel: 13109203A

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/29/2003 FRAMING Approved IVRS - Inspection 0000*
01/24/2003 FRAMING Denied IVRS - Inspection 0999*1.) SEE PREVIOUS NOTES.
2.) 24" SEPERATION OR APPROVED FIRE STOP SYSTEM IS REQUIRED ON STEEL BOXES.
01/22/2003 FRAMING Partial Approval IVRS - Inspection 0000*1.) PROVIDE COPY OF FIRE STOP SYSTEM YOU WILL BE USING FOR FIRE BARRIER.
2.) YOU MAY NOT INSTALL 4" X 4" STEEL BOXES BACK TO BACK IN FIRE WALL. 24" SEPERATION IS REQUIRED FOR BOXES IN SAME STUD BAY.
BOXES MAY BE CLOSER IF YOU USE AN APPROVED FIRE STOP SYSTEM. PLEASE PROVIDE COPY OF SYSTEM YOU INTEND TOUSE.
3.) NO NO COVER FIRE BARRIEN UNTIL REINSPECTED.